| Monitoring relay, can be mounted to Contactor 3RT2, Size S00 basic, analog adjustment Apparent current monitoring 1.6-16 A, 20-400 Hz, 2-phase Supply 24 V AC/DC 1 change-over contact Monitoring for Current overshoot and undershoot Phase failure, Cable break with or without fault buffer ON delay 0-60 s Noise pulse suppression 0-30 s Switching hysteresis 6% spring-type connection system |
Product brand name | SIRIUS |
Product designation | Monitoring relays |
Design of the product | analogically adjustable, 2-phase current monitoring |
Product type designation | 3RR2 |
General technical data |
Size of contactor can be combined company-specific | S00 |
Operating apparent output rated value | 4 V·A |
Insulation voltage | |
for overvoltage category III according to IEC 60664 | |
— with degree of pollution 3 rated value | 690 V |
Surge voltage resistance rated value | 6 kV |
Protection class IP | |
on the front | IP20 |
of the terminal | IP20 |
Shock resistance | 15g / 11 ms |
Mechanical service life (switching cycles) | |
typical | 10 000 000 |
Electrical endurance (switching cycles) | |
at AC-15 at 230 V typical | 100 000 |
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750 | K |
Reference code acc. to DIN EN 81346-2 | K |
Reference code acc. to DIN EN 61346-2 | K |
Relative repeat accuracy | 2 % |
Supply voltage |
Type of voltage of the supply voltage | AC/DC |
Supply voltage 1 at AC | |
at 50 Hz rated value | 24 V |
at 60 Hz rated value | 24 V |
Supply voltage 1 at DC rated value | 24 V |
Supply voltage frequency | |
1 | 50 ... 60 Hz |
Measuring circuit |
Type of current for monitoring | AC |
Adjustable pick-up value current | |
1 | 1.6 ... 16 A |
2 | 1.6 ... 16 A |
Adjustable response delay time | |
when starting | 0 ... 60 s |
with lower or upper limit violation | 0 ... 30 s |
Precision |
Temperature drift per °C | 0.1 %/°C |
Communication/ Protocol |
Protocol is supported | |
IO-Link protocol | No |
Type of voltage supply via input/output link master | No |
Auxiliary circuit |
Number of CO contacts | |
for auxiliary contacts | 1 |
Operating current of auxiliary contacts at AC-15 | |
at 24 V | 3 A |
at 230 V | 3 A |
at 400 V | 3 A |
Operating current of auxiliary contacts at DC-13 | |
at 24 V | 1 A |
at 125 V | 0.2 A |
at 250 V | 0.1 A |
Contact rating of auxiliary contacts according to UL | B300 / R300 |
Main circuit |
Operating power | |
rated value | 2.5 W |
Outputs |
Operating current at 17 V minimum | 5 mA |
Electromagnetic compatibility |
EMC emitted interference | |
acc. to IEC 60947-1 | ambience A (industrial sector) |
EMI immunity | |
acc. to IEC 60947-1 | ambience A (industrial sector) |
Safety related data |
Protection against electrical shock | finger-safe |
Connections/Terminals |
Product function | |
removable terminal for main circuit | No |
removable terminal for auxiliary and control circuit | Yes |
Type of electrical connection | |
for main current circuit | spring-loaded terminals |
for auxiliary and control current circuit | spring-loaded terminals |
Type of connectable conductor cross-sections | |
for main contacts | |
— solid | 1x (0.5 ... 4 mm²) |
— finely stranded with core end processing | 1x (0.5 ... 2.5 mm²) |
— finely stranded without core end processing | 1x (0.5 ... 2.5 mm²) |
at AWG conductors for main contacts | 1x (20 ... 12) |
Connectable conductor cross-section for main contacts | |
single or multi-stranded | 0.5 ... 4 mm² |
finely stranded with core end processing | 2.5 ... 2.5 mm² |
finely stranded without core end processing | 0.5 ... 2.5 mm² |
Type of connectable conductor cross-sections | |
for auxiliary contacts | |
— solid | 1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²) |
— finely stranded with core end processing | 2x (0.25 ... 1.5 mm²) |
— finely stranded without core end processing | 2x (0.25 ... 1.5 mm²) |
at AWG conductors for auxiliary contacts | 2x (24 ... 16) |
AWG number as coded connectable conductor cross section | |
for main contacts | 20 ... 12 |
Tightening torque | |
with screw-type terminals | 0.8 ... 1.2 N·m |
Installation/ mounting/ dimensions |
Mounting position | any |
Mounting type | direct mounting |
Height | 90 mm |
Width | 45 mm |
Depth | 80 mm |
Required spacing | |
with side-by-side mounting | |
— forwards | 0 mm |
— Backwards | 0 mm |
— upwards | 0 mm |
— downwards | 0 mm |
— at the side | 0 mm |
for grounded parts | |
— forwards | 6 mm |
— Backwards | 0 mm |
— upwards | 0 mm |
— at the side | 6 mm |
— downwards | 0 mm |
for live parts | |
— forwards | 6 mm |
— Backwards | 0 mm |
— upwards | 0 mm |
— downwards | 0 mm |
— at the side | 6 mm |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Ambient temperature | |
during operation | -25 ... +60 °C |
during storage | -40 ... +80 °C |