3RR2142-2AA30
CURRENT MON. S0 BASIC 24V UC SPRING

From SIEMENS

Monitoring relay, can be mounted to Contactor 3RT2, Size S0 basic, analog adjustment Apparent current monitoring 4...40 A, 50...60 Hz, 2-phase Supply 24 V AC/DC 1 change-over contact Monitoring for Current overshoot and undershoot Phase failure, Cable break with or without fault buffer ON delay 0-60 s Noise pulse suppression 0-30 s Switching hysteresis 6% spring-type connection system
Product brand nameSIRIUS
Product designationMonitoring relays
Design of the productanalogically adjustable, 2-phase current monitoring
Product type designation3RR2
General technical data
Size of contactor can be combined company-specificS0
Operating apparent output rated value4 V·A
Insulation voltage
for overvoltage category III according to IEC 60664
— with degree of pollution 3 rated value690 V
Surge voltage resistance rated value6 kV
Protection class IP
on the frontIP20
of the terminalIP20
Shock resistance15g / 11 ms
Mechanical service life (switching cycles)
typical10 000 000
Electrical endurance (switching cycles)
at AC-15 at 230 V typical100 000
Reference code acc. to DIN 40719 extended according to IEC 204-2 acc. to IEC 750K
Reference code acc. to DIN EN 81346-2K
Reference code acc. to DIN EN 61346-2K
Relative repeat accuracy2 %
Supply voltage
Type of voltage of the supply voltageAC/DC
Supply voltage 1 at AC
at 50 Hz rated value24 V
at 60 Hz rated value24 V
Supply voltage 1 at DC rated value24 V
Supply voltage frequency
150 ... 60 Hz
Measuring circuit
Type of current for monitoringAC
Adjustable pick-up value current
14 ... 40 A
24 ... 40 A
Adjustable response delay time
when starting0 ... 60 s
with lower or upper limit violation0 ... 30 s
Precision
Temperature drift per °C0.1 %/°C
Communication/ Protocol
Protocol is supported
IO-Link protocolNo
Type of voltage supply via input/output link masterNo
Auxiliary circuit
Number of CO contacts
for auxiliary contacts1
Operating current of auxiliary contacts at AC-15
at 24 V3 A
at 230 V3 A
at 400 V3 A
Operating current of auxiliary contacts at DC-13
at 24 V1 A
at 125 V0.2 A
at 250 V0.1 A
Contact rating of auxiliary contacts according to ULB300 / R300
Main circuit
Operating power
rated value2.5 W
Outputs
Operating current at 17 V minimum5 mA
Electromagnetic compatibility
EMC emitted interference
acc. to IEC 60947-1ambience A (industrial sector)
EMI immunity
acc. to IEC 60947-1ambience A (industrial sector)
Safety related data
Protection against electrical shockfinger-safe
Connections/Terminals
Product function
removable terminal for main circuitNo
removable terminal for auxiliary and control circuitYes
Type of electrical connection
for main current circuitspring-loaded terminals
for auxiliary and control current circuitspring-loaded terminals
Type of connectable conductor cross-sections
for main contacts
— solid1x (1 ... 10 mm²)
— finely stranded with core end processing1x (1 ... 6 mm²)
— finely stranded without core end processing1x (1 ... 6 mm²)
at AWG conductors for main contacts1x (18 ... 8)
Connectable conductor cross-section for main contacts
single or multi-stranded1 ... 10 mm²
finely stranded with core end processing1 ... 6 mm²
finely stranded without core end processing1 ... 6 mm²
Type of connectable conductor cross-sections
for auxiliary contacts
— solid1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)
— finely stranded with core end processing2x (0.25 ... 1.5 mm²)
— finely stranded without core end processing2x (0.25 ... 1.5 mm²)
at AWG conductors for auxiliary contacts2x (24 ... 16)
AWG number as coded connectable conductor cross section
for main contacts18 ... 8
Tightening torque
with screw-type terminals0.8 ... 1.2 N·m
Installation/ mounting/ dimensions
Mounting positionany
Mounting typedirect mounting
Height109 mm
Width45 mm
Depth92 mm
Required spacing
with side-by-side mounting
— forwards0 mm
— Backwards0 mm
— upwards0 mm
— downwards0 mm
— at the side0 mm
for grounded parts
— forwards6 mm
— Backwards0 mm
— upwards6 mm
— at the side6 mm
— downwards6 mm
for live parts
— forwards6 mm
— Backwards0 mm
— upwards6 mm
— downwards6 mm
— at the side6 mm
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Ambient temperature
during operation-25 ... +60 °C
during storage-40 ... +80 °C