6ES7671-0RC08-0YA0
SIMATIC WinAC RTX 2010

From SIEMENS

SIMATIC WinAC RTX 2010, single license for 1 installation, R-SW, SW and documentation on DVD, license key on USB flash drive, Class A, 3 languages (de,en,fr), executable in Windows XP SP2, SP3 or Windows 7 32-bit, incl. InterValzero RTX, Reference HW: SIMATIC PC
General information
Product type designationRTX 2010
Firmware versionV4.6
Engineering with
Programming packageSTEP 7 V5.5 or higher / iMap V3.0 SP1; STEP 7 in TIA Portal V13 or higher
Memory
Type of memoryRAM
Work memory
integrated (for program)4 Mbyte; Adjustable; depends on Non Paged Memory Pool
integrated (for data)4 Mbyte; Adjustable; depends on Non Paged Memory Pool
Load memory
integrated RAM, max.8 Mbyte; Adjustable; depends on Non Paged Memory Pool
CPU processing times
for bit operations, typ.0.004 µs; Typical
for fixed point arithmetic, typ.0.003 µs; Typical
for floating point arithmetic, typ.0.004 µs; Typical
Reference platformPentium 4, 2.4 GHz
CPU-blocks
DB
Number, max.65 535; Limited only by RAM set for data
Size, max.64 kbyte
FB
Number, max.65 536; Limited only by RAM set for code
Size, max.64 kbyte
FC
Number, max.65 536; Limited only by RAM set for code
Size, max.64 kbyte
OB
Number, max.Limited only by RAM set for code
Size, max.64 kbyte
Number of free cycle OBs1; OB 1
Number of time alarm OBs1; OB 10
Number of delay alarm OBs1; OB 20
Number of cyclic interrupt OBs9; OB 30-38
Number of process alarm OBs1; OB 40
Number of ODK OBs3; OB 52-54
Number of DPV1 alarm OBs3; OB 55-57
Number of isochronous mode OBs2; OB 61-62
Number of startup OBs2; OB 100, 102
Number of asynchronous error OBs7; OB 80, 82-85, 86, 88
Number of synchronous error OBs2; OB 121, 122
Nesting depth
per priority class24
additional within an error OB24
Counters, timers and their retentivity
S7 counter
Number2 048
Retentivity
— adjustableYes
— lower limit0
— upper limit2 047
— preset8
Counting range
— lower limit0
— upper limit999
IEC counter
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
S7 times
Number2 048
Retentivity
— adjustableYes
— lower limit0
— upper limit2 047
— preset0
Time range
— lower limit10 ms
— upper limit9 990 s
IEC timer
presentYes
TypeSFB
NumberUnlimited (limited only by RAM capacity)
Data areas and their retentivity
Retentivity without UPS and PS Extension Board128 kbyte with SIMATIC IPC427C and HMI IPC477C; further SIMATIC PCs on request
Retentivity with UPSall data
Flag
Number, max.16 kbyte
of which retentiveMB 0 to MB 16383
Retentivity presetMB 0 to MB 15
Number of clock memories8
Data blocks
Retentivity presetYes
Local data
adjustable, max.64 kbyte
preset32 kbyte
per priority class, max.61 440 byte
Address area
I/O address area
Inputs16 kbyte
Outputs16 kbyte
Process image
Inputs, adjustable8 kbyte; 16 KB with STEP 7 V5.5 SP3 or higher
Outputs, adjustable8 kbyte; 16 KB with STEP 7 V5.5 SP3 or higher
Inputs, default512 byte
Outputs, default512 byte
Subprocess images
Number of subprocess images, max.15
Digital channels
Inputs128 000
Outputs128 000
Analog channels
Inputs8 000
Outputs8 000
Hardware configuration
Number of operable FMs and CPs (recommended)
FMFM distributed: FM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2
CP, PtP2; CP 340, CP 341 distributed
CP, LANOver PC CP
Submodules
Number of submodules, max4
— of which PROFIBUS, max.4; Supported interfaces: see 1st and 2nd interface
— of which Industrial Ethernet, max.1; Supported interfaces: see 3rd and 4th interface
Time of day
Clock
Hardware clock (real-time)Yes
retentive and synchronizableYes
Operating hours counter
Number8
Clock synchronization
supportedYes
to PC-CP, slaveYes
on Ethernet via NTPYes
1. Interface
Interface typeCP 5611, CP 5611-A2, CP 5612, CP 5621, CP 5622, integrated PROFIBUS interface of the SIMATIC PC
PhysicsRS 485 / PROFIBUS
IsolatedYes
Number of simultaneously operable CPs, max.1
Protocols
MPINo
PROFIBUS DP masterYes
PROFIBUS DP slaveNo
PROFIBUS DP master
Number of connections, max.8
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.64
Services
— PG/OP communicationYes
— RoutingYes
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationYes
— S7 communication, as clientYes
— S7 communication, as serverYes
— Isochronous modeYes
— SYNC/FREEZEYes
— Activation/deactivation of DP slavesYes
— Direct data exchange (slave-to-slave communication)Yes
— DPV0Yes
— DPV1Yes
Address area
— Inputs, max.16 kbyte
— Outputs, max.16 kbyte
User data per DP slave
— Inputs, max.244 byte
— Outputs, max.244 byte
2. Interface
Interface typeCP 5613, CP 5613-A2, CP 5613-A3, CP 5603, CP 5623
PhysicsRS 485 / PROFIBUS
IsolatedYes
Number of simultaneously operable CPs, max.4
Protocols
MPINo
PROFIBUS DP masterYes
PROFIBUS DP slaveNo
PROFIBUS DP master
Number of connections, max.50
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.125
Services
— PG/OP communicationYes
— RoutingYes
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationYes
— S7 communication, as clientYes
— S7 communication, as serverYes
— EquidistanceYes; Only in conjunction with isochronous mode
— Isochronous modeYes
— SYNC/FREEZEYes
— Activation/deactivation of DP slavesYes
— Direct data exchange (slave-to-slave communication)Yes
— DPV0Yes
— DPV1Yes
Address area
— Inputs, max.16 kbyte
— Outputs, max.16 kbyte
User data per DP slave
— Inputs, max.244 byte
— Outputs, max.244 byte
3. Interface
Interface typePROFINET
PhysicsEthernet
IsolatedYes
Number of simultaneously operable CPs, max.1; Intel Pro/1000 (Intel 82571EB, 82573L, 82574L, 82541PI; non-shared IRQ required); Intel i210T; integrated IE interface SIMATIC PC IPC4x7C, IPC6x7C, IPC8x7C, IPC2x7D, IPC4x7D, IPC6x7D, IPC8x7D, IPC547E
automatic detection of transmission rateYes; 10/100 Mbit/s
AutonegotiationYes
AutocrossingYes
Interface types
Number of ports1
integrated switchNo
Media redundancy
supportedNo
Protocols
PROFINET IO ControllerYes
PROFINET IO DeviceNo
PROFINET CBAYes
Open IE communicationYes
PROFINET IO Controller
Transmission rate, max.100 Mbit/s
Services
— PG/OP communicationYes
— S7 routingYes
— S7 communicationYes
— Isochronous modeNo
— Open IE communicationYes
— IRTNo
— Prioritized startupYes
— Number of IO devices with prioritized startup, max.32
— Number of connectable IO Devices for RT, max.128
— of which in line, max.128
— Activation/deactivation of IO DevicesYes
— Number of IO Devices that can be simultaneously activated/deactivated, max.8
— IO Devices changing during operation (partner ports), supportedYes
— Device replacement without swap mediumYes
— Send cycles1 ms
— Updating time1 to 512 ms (minimum value depends on communication share set for PROFINET I/O, on the number of I/O devices, and on the volume of configured user data)
Address area
— Inputs, max.16 kbyte
— Outputs, max.16 kbyte
— User data per address area, max.2 kbyte
— User data consistency, max.256 byte
PROFINET CBA
acyclic transmissionYes
cyclic transmissionYes
Open IE communication
Number of connections, max.32
Local port numbers used at the system end0, 20, 21, 23, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535
Keep-alive function, supportedYes
SIMATIC communication
Number of connections, max.16
4. Interface
Interface typePROFINET
PhysicsEthernet
IsolatedYes
Number of simultaneously operable CPs, max.1; CP 1616 (hardware release 8 or higher), CP 1604 (hardware release 7 or higher), integrated PROFINET interface of SIMATIC IPC and S7-mEC
automatic detection of transmission rateYes; 10/100 Mbit/s
AutonegotiationYes
AutocrossingYes
Change of IP address at runtime, supportedYes
Interface types
Number of ports3
integrated switchYes
Media redundancy
supportedYes
Switchover time on line break, typ.200 ms
Number of stations in the ring, max.50
Protocols
PROFINET IO ControllerYes
PROFINET IO DeviceNo
PROFINET CBAYes
Open IE communicationYes
Web serverYes
PROFINET IO Controller
Transmission rate, max.100 Mbit/s
Services
— PG/OP communicationYes
— S7 routingYes
— S7 communicationYes
— Isochronous modeYes
— Open IE communicationYes
— Prioritized startupYes
— Number of IO devices with prioritized startup, max.32
— Number of connectable IO Devices, max.256
— Of which IO devices with IRT, max.64
— of which in line, max.32
— Number of IO Devices with IRT and the option "high flexibility"64
— of which in line, max.32
— Number of connectable IO Devices for RT, max.256
— of which in line, max.256
— Activation/deactivation of IO DevicesYes
— Number of IO Devices that can be simultaneously activated/deactivated, max.8
— IO Devices changing during operation (partner ports), supportedYes
— Device replacement without swap mediumYes
— Send cycles250 µs, 500 µs, 1 ms
— Updating time0.25...512 depending on the send cycle
Address area
— Inputs, max.16 kbyte
— Outputs, max.16 kbyte
— User data per address area, max.2 kbyte
— User data consistency, max.256 byte
Open IE communication
Number of connections, max.32
Local port numbers used at the system end0, 20, 21, 25, 80, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534, 65535
SIMATIC communication
Number of connections, max.32
Protocols
Open IE communication
TCP/IPYes
— Number of connections, max.32
— Data length for connection type 01H, max.Not supported
— Data length for connection type 11H, max.65 534 byte
— Data length, max.65 534 byte
ISO-on-TCP (RFC1006)Yes
— Number of connections, max.32
— Data length, max.65 534 byte
UDPYes
— Number of connections, max.32
— Data length, max.1 472 byte
Web server
supportedYes
User-defined websitesNo
Number of HTTP clients2
Isochronous mode
Isochronous operation (application synchronized up to terminal)Yes
EquidistanceYes
Number of DP masters with isochronous mode2
User data per isochronous slave, max.128 byte
shortest clock pulse2.2 ms; 2.2 ms without partial process image; 2.2 ms with partial process image
Communication functions
PG/OP communicationYes
Data record routingYes; only with CP 5611 or integrated PROFIBUS interface of the SIMATIC PC
Global data communication
supportedNo
S7 basic communication
supportedNo
S7 communication
supportedYes
as serverYes
as clientYes
User data per job, max.64 kbyte; when using BSEND/USEND
PROFINET CBA (at set setpoint communication load)
Setpoint for the CPU communication load20 %
Number of remote interconnection partners64
Number of functions, master/slave30
Total of all master/slave connections1 000
Data length of all incoming connections master/slave, max.6 800 byte
Data length of all outgoing connections master/slave, max.6 800 byte
Number of device-internal and PROFIBUS interconnections500
Data length of device-internal und PROFIBUS interconnections, max.4 000 byte
Data length per connection, max.1 400 byte
Remote interconnections with acyclic transmission
— Sampling frequency: Sampling time, min.500 ms
— Number of incoming interconnections100
— Number of outgoing interconnections100
— Data length of all incoming interconnections, max.2 000 byte
— Data length of all outgoing interconnections, max.2 000 byte
— Data length per connection, max.1 400 byte
Remote interconnections with cyclic transmission
— Transmission frequency: Transmission interval, min.10 ms
— Number of incoming interconnections200
— Number of outgoing interconnections200
— Data length of all incoming interconnections, max.4 800 byte
— Data length of all outgoing interconnections, max.4 800 byte
— Data length per connection, max.250 byte
HMI variables via PROFINET (acyclic)
— Number of stations that can log on for HMI variables (PN OPC/iMap)3
— HMI variable updating500 ms
— Number of HMI variables200
— Data length of all HMI variables, max.2 000 byte
PROFIBUS proxy functionality
— supportedYes
— Number of linked PROFIBUS devices16
— Data length per connection, max.240 byte; Slave-dependent
Number of connections
overall96
S7 message functions
Number of login stations for message functions, max.62
SCAN procedureNo
Process diagnostic messagesYes; ALARM_S, ALARM_SQ, ALARM_D, ALARM_DQ
simultaneously active Alarm-S blocks, max.20; of a total of 20 for all SFCs
Alarm 8-blocksYes
Number of instances for alarm 8 and S7 communication blocks, max.4 000
Process control messagesNo
Number of archives that can log on simultaneously (SFB 37 AR_SEND)32
Test commissioning functions
Status blockYes
Single stepYes
Number of breakpoints20
Status/control
Status/control variableYes
Forcing
ForcingNo
Diagnostic buffer
presentYes
Number of entries, max.
— adjustableYes
— preset120
Hardware requirement
Hardware requiredPC with color monitor, keyboard, mouse or pointing device for Windows
Processor
ProcessorIntel Celeron M, 900 MHz or compatible
— Multi-processor systemYes; Dual Pentium, CoreDuo, Core2Duo or compatible
— Hyper-threadingYes
Memory
Main memory, min.1 Gbyte; WES7: 2 GB
Required memory on hard disk100 Mbyte
Operating systems
pre-installed operating system
Windows NT 4.0No
Windows 2000No
Windows VistaNo
Windows XPYes; Professional, SP2 and SP3
Windows XP EmbeddedYes; With the delivery image of the SIMATIC PC
— supported HAL types under Windows XPACPI uniprocessor PC, ACPI multiprocessor PC, MPS multiprocessor PC
Windows 7Yes; Professional, Enterprise, Ultimate (only 32 bit)
Windows Embedded Standard 7Yes; With delivery image of SIMATIC PC (only 32-bit)
Configuration
Configuration software
STEP 7Yes; V5.5 and higher, Engineering Tools (optional)
Programming
Nesting levels8
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— CFCYes
— GRAPHYes
— HiGraph®Yes
Software libraries
— Easy Motion ControlYes
— Software redundancyYes; As of V1.2, only operation of WinAC RTX with WinAC RTX
Number of simultaneously active SFCs
— DPSYC_FR20; of a total of 20 for all SFCs
— D_ACT_DP20; of a total of 20 for all SFCs
— RD_REC20; of a total of 20 for all SFCs
— WR_REC20; of a total of 20 for all SFCs
— WR_PARM20; of a total of 20 for all SFCs
— PARM_MOD20; of a total of 20 for all SFCs
— WR_DPARM20; of a total of 20 for all SFCs
— DPNRM_DG20; of a total of 20 for all SFCs
— RDSYSST20; of a total of 20 for all SFCs
Number of simultaneously active SFBs
— RDREC20; of a total of 20 for all SFBs
— WRREC20; of a total of 20 for all SFBs
Know-how protection
User program protection/password protectionYes
Open Development interfaces
CCX (Custom Code Extension)Yes; WinAC ODK V4.2 or higher
CMI (Controller Management Interface)Yes; WinAC ODK V4.2 or higher
SMX (Shared Memory Extension)Yes; WinAC ODK V4.2 or higher
— Inputs4 kbyte
— Outputs4 kbyte
Weights
Weight, approx.100 g; With packaging

External links